- 2HP
- 3HP
- 5HP
- 6HP
Horse Power
2HP With EVI (Enhanced Vapor Injection)
Power Supply
380V/50Hz/3N
220V/60Hz/3Phase
Temperature Range
-35℃ ~ 10℃
Feature
- DC Inverter Condensing Unit
- Hot Gas Defrost
- Inbuilt Electric Cabinet
- Precharged Refrigerant (R404A)
- Integrated Electric Expansion Valve
- Remote Control Available
Horse Power
3HP With EVI (Enhanced Vapor Injection)
Power Supply
380V/50Hz/3N
220V/60Hz/3N
Temperature Range
-35℃ ~ 10℃
Feature
- DC Inverter Condensing Unit
- Hot Gas Defrost
- Inbuilt Electric Cabinet
- Precharged Refrigerant (R404A)
- Integrated Electric Expansion Valve
- Remote Control Available
Horse Power
5HP With EVI (Enhanced Vapor Injection)
Power Supply
220V/60Hz/3N
380V/50Hz/3N
Temperature Range
-35℃ ~ 0℃
Feature
- DC Inverter Condensing Unit
- Hot Gas Defrost
- Inbuilt Electric Cabinet
- Precharged Refrigerant (R404A)
- Integrated Electric Expansion Valve
- Remote Control Available
Horse Power
6HP With EVI (Enhanced Vapor Injection)
Power Supply
380V/50Hz/3N
220V/60Hz/3N
Temperature Range
-35℃ ~ 10℃
Feature
- DC Inverter Condensing Unit
- Hot Gas Defrost
- Inbuilt Electric Cabinet
- Precharged Refrigerant (R404A)
- Integrated Electric Expansion Valve
- Remote Control Available






Doluyo Cold Room Solutions
How to select your cold room
1. What is the application of the cold room?
It will affect the temperature of cold room needed to be, and the choice of thickness of pu panel and material covered on panel.
2. What is the size of the cold room?
It will affect the choice of condensing unit and air cooler, basing on the cold room temperature
3. Which country will the cold room be located in? How about the climate?
It will affect the choice of voltage and condenser, if the temperature is high all the year, we need to choose condenser with bigger evaporation area.
Application | Room Temperature |
---|---|
Fruit & Vegetable | -5°C ~ 8°C |
Medicine & Vaccine | 0°C ~ 5°C |
Ice cream & Ice Storage | -10°C ~ -5°C |
Frozen meat storage | -25°C ~ -18°C |
Fresh meat storage | -40°C ~ -30°C |
Cold Room Structure Graph
Cold Room Structure
Doluyo cold room consistes of cold room panel (PU sandwich panel), cold room door, balance window, all in one condensing unit, evaporator (air cooler), control pad.
Everything you need for condensing unit for example, EEV, electric power cabinet, etc are integreted into the condensing unit.
Upgrade your outdoor refrigeration units with Doluyo's innovative box-type structure, designed to provide superior protection against dust and rain. Our cutting-edge enclosure ensures that vital components, such as the compressor, remain dry and secure, even during adverse weather conditions. This enhancement is crucial for maintaining the integrity of your refrigeration system. Keep in mind, with open-type refrigeration setups, there's a significant risk of water ingress leading to potential compressor damage. Choose Doluyo's protective solutions to safeguard your investment and enhance the longevity of your refrigeration equipment.
Cold Room Panel/PU Panel
Panel Thickness (mm) | 50 | 75 | 100 | 150 | 250 |
---|---|---|---|---|---|
Stainless steel (mm) | 0.56 | 0.66 | 0.76 | 0.86 | 0.96 |
Color steel (mm) | 0.426 | 0.526 | 0.5 | 0.6 | 0.8 |
Galvanized steel (mm) | 1.0 | 1.2 | 1.5 | - | - |
Salinization steel (mm) | 0.5 | 0.6 | - | - | - |
Embossed aluminum (mm) | 0.6 | 0.8 | - | - | - |
Non-slip aluminum (mm) | 3 | 5 | - | - | - |
KNOW US BETTER
DC Inverter Condensing Unit Video

PRODUCT DIMENSIONS.
TECHNICAL PARAMETERS.
Model | DCF030AM-CE3 | |||||
---|---|---|---|---|---|---|
Compressor Operating Frequency | 30Hz | 75Hz | 90Hz | |||
Cooling Capacity & Electric Power |
Evaporating Temperature ℃ |
10 |
Cooling Capacity (W) |
5364 | 13860 | 16470 |
Electric Power (W) |
1657 | 3872 | 4812 | |||
0 |
Cooling Capacity (W) |
3862 | 9918 | 11832 | ||
Electric Power (W) |
1554 | 3631 | 4513 | |||
-10 |
Cooling Capacity (W) |
2697 | 6970 | 8315 | ||
Electric Power (W) |
1732 | 4776 | 5697 | |||
-20 |
Cooling Capacity (W) |
1732 | 4776 | 5697 | ||
Electric Power (W) |
1308 | 3058 | 3801 | |||
Noise | dB(A) | 60 | 63 | 65 | ||
Room Temp. Range | ℃ | -20 ~ 10 | ||||
Ambient Temp. Range | ℃ | -10 ~ 43 | ||||
Power Supply | 380V/3N~/50Hz | |||||
Refrigerant | R404 | |||||
Compressor | Type | Hermetic Scrollcom Pressor | ||||
House Power | HP | 3 | ||||
Condenser Fan | Type | High Efficiency Low Noise Axial Fan | ||||
QTY | PCS | 1 | ||||
Power | W | 60 | ||||
Pipe Connection | Liquid Line | mm | Φ12.7 | |||
Gas Line | mm | Φ15.88 | ||||
Unit Power Cord | mm | 2.5mm² x 5 | ||||
Dimensions (LxDxH) | PCS | 952x438x823 | ||||
Net Weight | kg | 90 |
FAQ .
Southeast Asia(5.00%), South Asia(2.00%), Southern Europe(2.00%), Mid East(2.00%), North America(1.00%), Africa(1.00%), South America(1.00%), Northern Europe(1.00%), Central America(1.00%), Eastern Europe(1.00%), Western Europe(1.00%), Eastern Asia(1.00%), Oceania(1.00%).
There are total about 101-200 people in our office.
Accepted Payment Currency:USD,EUR,JPY,CAD,AUD,HKD,GBP,CNY,CHF;
Accepted Payment Type: T/T,L/C,PayPal,Western Union,Cash;
Language Spoken:English,Chinese,Spanish,Japanese,Portuguese,German,Arabic,French,Russian,Korean,Hindi,Italian